ECI Nova Modular Inverters 48 Vdc 1.25 kVA

Nova ECI is a small modular inverter offering many opportunities to design a solution that perfectly fits your needs. The ECI technology offers both AC and DC inputs to provide a perfect AC power while reducing the number of power conversion (the module operates under normal condition with the AC input delivering a 96% efficiency)! In conjunction with the DC input, it provides an excellent AC backup solution.

From 1 to 32 modules, with several options available (manual external by-pass and AC distribution), the Nova ECI is also hot-swappable meaning a very easy and cheap maintenance. The modules are delivered with our new monitoring solution.

Applications

  • All business critical applications from 1.25 kVA to 40 kVA.
  • The module can be integrated into shelves to design 1 phase (230 Vac) or 3 phases (3×400 Vac) configuration with different power output.
  • We already designed 3 shelves configuration: 5 modules (6.25 kVA, 1 phase), 4 modules (5 kVA, 1 phase) with the monitoring included and 9 modules (11.25 kVA, 1P) with the monitoring.

SPECIFICATIONS TABLE

Power
AC Output Power
Nominal Output power (VA) / (W) 1250 VA / 1000 W
Short time overload capacity 125% (15 seconds)
Admissible load power factor Full power rating from 0 inductive to 0 capacitive
DC Input Specifications
DC voltage: Nominal / range 48 VDC / (40-60V)*
Nominal current (at 48 Vdc and 2400 W output) 22.3 A
Maximum input current (for 15 second) / voltage ripple 27.5 A / < 10 mV RMS
AC Input Specifications
Nominal voltage (AC) 230 V
Voltage range (AC) 150 – 265 V
Brownout 800 W @ 150 Vac / 1000 W @ >190 Vac linear decreasing
Power factor > 99%
Frequency range (selectable) / synchronization range 50 Hz (range 47 – 53 Hz) / 60 Hz (range 57 – 63 Hz)
AC Output Specifications
Nominal voltage (AC**) Adjustable: 220 VAC – 240 VAC
Frequency / frequency accuracy 50 or 60 Hz / 0.03%
Total harmonic distortion (resistive load) < 3%
Load impact recovery time (10% – 90%) <= 0.4 ms
Nominal current 5.4 A @ 230 Vac
Crest factor at nominal power 3 : 1 for load P.F. <=0.7
Short circuit clear up capacity 0-20 ms 20 A for 20 msec – Available while Mains is available at AC input port / 16 A DC/AC
Short circuit current after >20 ms -15 s 7 A RMS
AC output voltage stability  ±1% from 10% to 100% load
In Transfer Performance
Max. voltage interruption / total transient voltage duration (max) 0 s / 0 s
Signaling & Supervision
Display Synoptic LED
Alarms output / Supervision 2 dry contacts, 2 digital inputs / Inview GW (3 LEDs) or Inview S (2.8” touchscreen)
Remote on / off On rear terminal of the shelf
EMC EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8
ETSI EN 300386 v1.9.1
Safety EN62040-1
Cooling Forced
MTBF 240 000 hrs (MIL-217IF)
Efficiency (Typical): Enhanced power conversion / on line 96% / >92.5%
Dielectric strength DC/AC 4300 Vdc
RoHS Compliant
Environment ETSI EN 300019 / ETSI EN 300132.2
Altitude above sea without de-rating of power < 1500 m / derating > 1500 m – 0.8 % per 100 m / max 4000 m
Ambient temperature  -20 to 40° C
derating from 40°C to 65°C
Storage temperature / relative humidity  -40 to 70°C / 95%, non-condensing
Material (casing) Alu Zinc