80% of UPS failures are due to undetected battery problems. All batteries fail, its just a matter of time. If you’re operating mission critical systems and relying on the protection of a UPS and battery bank, then it has to make sense to have battery monitoring. It’s about peace of mind – knowing that the batteries are healthy and being constantly monitored. Knowing that everything has been done, that can be done, to protect your enterprise from the consequences of a power failure.
FEATURES
BMS-DC-LCDⅡ (Data Collector) | |
Display | Graphic Touch Screen |
Input Power Supply | 12Vdc |
Power Consumption | = 9W |
Communication Ports | Ethernet x 1, RS-485 Modbus RTU x 1 Output Dry Contact Port x 3, Input Dry Contact Port x 1 |
Monitoring RF Receiver | Up to 63 RF Receivers |
Manage Nodes | Maximum 750 nodes |
Storage Media | Up to16 Gigabyte SD/MMC Flash Memory Card |
Dimensions (WxHxD) | 260 mm x 150 mm x 57 mm/10.2″ x 5.9″ x 2.2″ |
WeightPower supply [10W]: | 0.85 kg / 1.9 lbs |
BMS-RFR (RF Receiver) | |
Input Power Supply | 12Vdc |
Power Consumption | ≤ 3W |
Receiving Interface | RF 2.4 GHz for wireless 1 |
Monitoring Nodes | Maximum 256 nodes |
Dimensions (WxHxD) | 129 mm x 70 mm x 35.5 mm / 5.1″ x 2.7″ x 1.4″ |
Weight | 0.4 kg / 0.9 lbs |
BMS-BMK (Battery Measure Kit) | |
Block Voltage | 2V/6V/12V |
Voltage Measurement Range | 1.48-4.00V/ 4.2-8.0V/8.5-16V |
Accuracy | ±5mV/±5mV/10mV |
Battery Impedance Resolution | see the datasheet |
Temperature Measurement | 0-100°C ±1°C / 32 |
Power Consumption | = 0.5 W |
Input Impedance | ≧ 1 MO |
Dimensions (WxHxD) | 100 mm x 27 mm x 70 mm / 3.9″ x 1.1″ x 2.8″ |
Weight | 0.1 kg / 3.4 ozs |
BMS-SMK (String Measure Kit) | |
Voltage Measurement Range | Up to 750Vdc |
Accuracy | ±0.2% of normal voltage |
Temperature Measurement 2 | 0-100°C ±1°C / 32 |
Current Measurement 3 | 0-3000 A |
Input Power Supply Range | 35-60 VDC |
Power Consumption | = 3 W |
Input Impedance | ≧ 1 MO |
Dimensions (WxHxD) | 100 mm x 27 mm x 70 mm / 3.9″ x 1.1″ x 2.8″ |
Weight | 0.09 kg / 3.1 ozs |
1 Maximum transmitting distance is rated at 50m/164ft in a non-concealed room or cabinet. Recommended distance is less than 20m/65ft for optimal performance.
2 Optional Temperature Sensor (TES) is required for temperature measurement. 3 Optional Hall Current Transformer (HCT) is required for battery current measurement. |