DAC6000 inverters are modular and may be integrated into the same cabinet as the OPUS DC power system for redundant, fault-tolerant performance when long life and long battery service are required.The DAC60000 inverters and corresponding systems are 90% efficient and compatible with most battery configurations and fit into standard 19″ rack and cabinet systems. They offer a modular approach, and can be combined with a static switch, manual by-pass, AC distribution and 3-phase synchronization modules based on unique customer requirements.
The OPUS Inverter system has a modular construction. The inverter modules can be combined with a static switch, manual bypass, AC distribution and 3-phase synchronization modules based on customer’s needs.The OPUS Inverter system can be integrated in the same cabinet as Efore DC power systems with advanced VIDI+ controller, temperature sensors and battery monitoring.
Model Number | Type | Power Level (VA) | Input Voltage (Vdc) | V1 Out Nom (V) | Output Current Max (A) | Cooling |
DAC62132VF | Inverter | 1000VA | 20 – 32 | 230 | 4.4 | Convection |
DAC62134VF | Inverter | 1000VA | 40 – 72 | 230 | 4.4 | Convection |
DAC62135VF | Inverter | 1000VA/700W | 88 – 150 | 230 | 4.4 | Convection |
DAC62136VF | Inverter | 1000VA/700W | 178-275 | 230 | 4.4 | Convection |
DAC62232VF | Inverter | 1200VA/800W | 20 – 32 | 230 | 5.2 | Fan |
DAC62234VF | Inverter | 1200VA/1200W | 40 – 72 | 230 | 5.2 | Fan |
DAC62235VF | Inverter | 1200VA/1200W | 88 – 150 | 230 | 5.2 | Fan |
DAC62236VF | Inverter | 1200VA/1200W | 178-275 | 230 | 5.2 | Fan |
BPU69130VF | Static Bypass 19″/6 6U | 6000 | 230VAC | 230 | 27 | Convection |
MBP68000 | Manual Bypass 19″/6 6U | 6000 | 230VAC | 230 | 27 | Convection |
MBP68200 | Manual Bypass 19″ 2U | 6000 | 230VAC | 230 | 27 | Convection |
Input Voltage | 24VDC 48/60VDC 110/125VDC 220VDC |
Nominal Power | 1000-1200VA |
Efficciency | 83-90% |
Load Power Factor | Full Power rating from inductive to 0 capacitive |
THD | <2% |
Isolation | Input-Chassis 1500 VAC (2000 VDC), Input-Output 3000 VAC (4000 VDC), Output-Chassis 1500 VAC (2000 VDC) |
Protection | Output current limiting, Overload and short circuit proof. Internal input and output fuses |
LED-indications | Input ON; Output ON; Output overloading, 4 levels; Overload/Fault |
Relay alarms | 2 relay contacts; |
Remote monitoring | Web interface, SNMP traps, SMTP mail alerts and Modbus TCP/IP through VIDI+ con- troller. Status information: for example input and output voltage, power, temperature, faults, etc. Parameter adjustment: limits, output voltage, overload, faults, etc. |
© Copyright Helios Power Solutions 2022