ICT200DF-20BRC Smart 10/10 GMT DC Load Distribution Panel

Brand: ICT Power

SKU: ICT200DF-20BRC
Note: This product is not available in the following regions: Australia
  • 200A continuous system rating / 100A per bus
  • +/-24 or +/-48 VDC
  • 20A GMT fuses per output (16A continuous)
  • TCP/IP remote management and power control of individual outputs
  • Ten fully managed outputs per bus
  • Software Demonstration 

Description

ICT200DF-20BRC

Distribution Series 3 – Smart 10/10 GMT DC Load Distribution Panel

The ICT200DF-20BRC is an intelligent, dual bus, DC load distribution GMT fuse panel with remote monitoring and power control over Ethernet. Each bus is rated at 100A continuous and provides 10 GMT fuse positions, each rated at 20 Amps maximum. The ICT200DF-20BRC is designed for sites requiring I.P.-based remote monitoring and power control of up to 20 connected loads.

Dual DC Distribution Bus

Dual voltages and polarities can be supported on a single panel, useful for sites requiring -48 and +48 or -48 and +24 volts DC to be distributed simultaneously. Alarms can be sent to multiple email accounts, and each output has definable load-shed settings. The network watchdog feature will ping up to 12 pre-determined I.P. addresses, such as a router, and power-cycle the device if not answered.

TCP/IP Remote Management

The ICT200DF-20BRC allows each connected load to be monitored, power cycled, or taken off-line. This functionality can be used to conserve power, troubleshoot devices, and reboot connected loads remotely, possibly preventing or delaying the need for a costly site visit. The on-board web server means there is no software to maintain, and SNMPv3 is also supported. Firmware can be updated remotely over Ethernet.

Main Features

  • 200A continuous system rating / 100A per bus
  • +/-24 or +/-48 VDC
  • 20A GMT fuses per output (16A continuous)
  • TCP/IP remote management and power control of individual outputs
  • Ten fully managed outputs per bus
  • Independent Form C alarm contacts for each bus
  • Remote firmware update capability
  • HTTPS, SMTP, SNMPv3 protocols supported
  • Monitoring and alarm reporting of each output for pinpointing of issues with connected loads
  • Each output has adjustable load-shed settings
  • Adjustable power-on sequencing
  • Site monitoring sensor inputs with alarm reporting
  • Data logging
  • 2-year warranty

Configurable Alarms

  • Channel over current threshold
  • Channel over/under current
  • Bus over current
  • Automatic load shedding
  • Bus over/under voltage threshold
  • Site monitoring input contact status

Recommended 1U Rack Mount DC Power Supplies for ICT200DF-20BRC DC Distribution Panel

Pro Series 1U Rack Mount DC Power Supply 12V 24V 48V

Compare

PRO 1U Rack Mount Battery Charger/DC UPS: 690W – 1200W

Platinum Series 1U Rack DC Power Supply 12V 24V 48V

Compare

Platinum Series AC/DC Power Supplies with TCP/IP Ethernet: 800W – 1600W

SPECIFICATIONS TABLE

Power Specifications
Operating Voltage Range (POS or NEG)20-60VDC
System Current Rating200A cont
A/B Bus Current Rating100A cont
Number of Outputs per Bus10
Max. GMT Fuse Size20A (1)
Continuous Load Rating16A per output

(1) GMT fuses not supplied by ICT

 

Mechanical
Form Factor1RU – 19 Inch rack mount
Dimensions L x W x H236 x 483 x 45 mm
Weight (lbs/kg)9.5 lbs / 4.3 kg
Input ConnectorsDual 1/4” – 20 studs with 0.625” spacing
Output ConnectorsCage clamp 10-22AWG

COMMUNICATIONS & CONTROL

Communications & Control 
EthernetTCP/IP built-in web server and graphical user interface, 10/100BASE-T, IEEE 802.3 compatible
Supported ProtocolsIPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMPv1/v2c/v3
SNMP PortsUDP Port 161, SNMP Traps: UDP Port 162
Firmware UpgradesUpgradeable over Ethernet
SecurityPassword protection, HTTPS encryption, TLS 1.2
20 Channel Output MonitoringCurrent draw measured and reported for each output, user definable under and over current alarms
Email and SMS AlertsMultiple email or text accounts, adjustable intervals
Data LoggingUp to 30 days at 1 minute sampling rate, csv file download, major event logging
Network WatchdogAutonomously ping up to 12 I.P. addresses and power-cycle output if no response, definable settings
Power Cycling and RebootingRemote on/off control of every output individually
Auto Restore ModeReturn to previous output settings after a power loss
Power-up Delay SequencingUser selectable 0 to 60 second delay between outputs
Auto Load SheddingEach output user definable, manual or auto restart

View Datasheet