Master Industrial AC UPS

30kVA – 80kVA DC BUS 220 VDC

Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.

Industrial environment

Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.

High ICC (short-circuit current)

The high short-circuit current (ICC = 3) makes it suitable for loads that require high current peaks during switch-on or during normal operation.

Continuous voltage 220 V

The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

Redundant ventilation

Redundant ventilation at 100% load is standard, ensuring operation with a normal load with half of the fans operating; in addition, each fan is monitored and an alarm signal is provided in the event of failure.
The Easy Source input features, the Battery Care System, and the flexibility and communications capabilities are the same as those of the conventional Master MPS range.

Isolation transformer
Synchronisation device (UGS)
Hot connection device (PSJ)
Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for extended runtimes
Top Cable Entry cabinets
IP rating IP31/IP42

SERIES TABLE

MODEL  NOMINAL POWER (Kva) ACTIVE POWER (Kw) DIMENSIONS 
MIM 30 30 24 800 x 800 x 1900
MIM 40 40 32 800 x 800 x 1900
MIM 60 60 48 1200 x 800 x 1900
MIM 80 80 64 1200 x 800 x 1900

SPECIFICATIONS TABLE

INPUT
Voltage 380-400-415 Vac, three-phase + N and 220-230-240 Vac single-phase + N
(input voltage recognition function)
Voltage tolerance 400 V ± 20%
Frequency 45 – 65 Hz
Power factor at full load > 0.93
Current distorsion < 6%
OUTPUT
Voltage 230 Vac single-phase
Voltage stability < 1% with linear load / < 3% with non-linear load
Frequency 50 Hz / 60 Hz
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Number of cells 108/114
Type VRLA AGM/GEL
Maximum charging voltage 274 V
Temperature compensation  -0,5 Vx°C