OPUS C 12U

Modular Battery Charger

OPUS C 12U are compact, 19″ rack-mount DC power systems that offer a robust, free convection cooled, N+1 redundant backup power solution for telecommunications, process industry, transmission and distribution substations and other critical infrastructure applications.

The OPUS C 12U is a 19″ self-contained rack-mount power system consisting of the MRC series rectifiers, VIDI+ controllers, mains and battery connections, and a wide selection of load distribution options. OPUS C systems are available in 24, 48, 60, 110, 125 and 220 VDC standard outputs and have a max output power of 8.0 kW.The systems meet IEC 60950-1 safety standards and the following EMC standards: Emissions: IEC/EN 61000-6-4, Immunity: IEC/EN 61000-6-2, Harmonics: IEC/EN 61000-3-2, and Voltage Fluctuations & Flicker: IEC/EN 61000-3-3.

The OPUS system can be connected to 3-phase TN, TT or IT power distribution systems. The nominal operating voltage of the system is 3*230/400 Vac, 50 Hz. With respect to other installation alternatives, please contact our sales or technical service. The installation location should fulfill the following requirements:

  • The operating ambient temperature range is -20°C to +40°C
  • The storage ambient temperature range is -45°C to +70°C
  • Relative humidity 5…95%, no condensation
  • Maximum altitude is 2000 m above sea level
  • Ventilation air shall not contain any corrosive substances, dissolving agents nor significant amount of dust etc.

Applications

  • Critical infrastructure
  • Power transmission substations
  • Power distribution substations
  • Railway signalling and substations
  • Process industries
  • Telecommunications
  • Mining
  • Oil & Gas

Case Study

Modular & Redundant Battery Chargers for Six Electrical Substations In Bangladesh

Features of CAB 716 

  • 48VDC Dual 3.2kW battery charger in a 45U 600mm W x 600mm D cabinet
  • Two 230VAC Mains Input Connections
  • Float Voltage of 56.8VDC configured for NiCd batteries
  • Single DC Distribution with 10 x 10A 2P load breakers with Auxiliary switches
  • Configured for redundancy by two +P95 blocking diodes
  •  Two 100A 2P Battery MCB’s, one for each battery
  • Temperature sensor with temperature compensation
  • A Low Voltage Disconnect set at 40VDC for each charger
  • End customer: Power grid company in Bangladesh
  • MODBUS
  • SNMP

SERIES TABLE

ModelPower Out Max (kW)Input Voltage (VAC)Output Voltage Range (VDC)Output Current Max (A)
OPUS C 24 5.5 R 12U F5.5180 – 27521 – 31229
OPUS C 48 8 R 12U F8180 – 27542 – 58164
OPUS C 48 8 R 12U P8180 – 27542 – 58164
OPUS C 60 8 R 12U P8180 – 27551 – 72134
OPUS C 110 8 R 12U F8180 – 27597-13272
OPUS C 220 8 R 12U F8180 – 275189-26536

SPECIFICATIONS TABLE

AC-connection3W + N + PE
Nominal voltage230 / 400 VAC
Range, full180 – 275 VAC
Range, reduced140 – 180 VAC
Frequency45 to 65 Hz
Internal protection16 A MCB / rectifier module
Mains terminalTerminal blocks 10 mm2
ProtectionIP 20
Option IP21
Controller user interfaceDisplay and local control in front panel
Distribution and ConnectionsBehind front panel
ColourFrame RAL 7037
Door RAL 7035
ColourFrame RAL 7012
DimensionsHeight 533 mm
Width 438 mm
Depth 370 mm
Dimensions, Wall mounting + IP21Height 350 mm
Width 482 mm
Depth 503 mm
Operating temperature-20°C … +45°C
Humidity max95% relative humidity, non-condensing
Altitude max2000 m above sea level
SafetyIEC/EN 60950-1
EMCEmissions: IEC/EN 61000-6-4
Immunity: IEC/EN 61000-6-2 Harmonic currents IEC/EN 61000-3-2 Voltage fluctuation & flicker:
IEC/EN 61000-3-3