The SENTINEL DUAL (High Power) range is available in 3.3kVA -4-5kVA -6kVA -8kVA – 10kVA single-phase models and 6.5-8-10kVA three-phase/single-phase models, with on-line double conversion (VFI) technology.The DIALOG DUAL range may be placed directly on the floor or mounted in 19” rackmount cabinets such as the Multi Shelter range. SENTINEL DUAL (High Power) is ideally suited for a whole range of applications from IT to security.

 

SERIES TABLE

Model Power Active Power Input Voltage
SDL 3300 3300 VA 2300 W 220-230-240 Vac
SDL 4000 4000 VA 2400 W 220-230-240 Vac
SDL 5000 5000 VA 4500 W 220-230-240 Vac
SDL 6000 6000 VA 5400 W 220-230-240 Vac
SDL 8000 8000 VA 7200 W 220-230-240 Vac
SDL 10000 10000 VA 9000 W 220-230-240 Vac
SDL 6500 TM 6500 VA 5850W 400 Vac three-phase + N
SDL 8000 TM 8000 VA 7200 W 400 Vac three-phase + N
SDL 10000 TM 10000 VA 9000 W 400 Vac three-phase + N

SPECIFICATIONS TABLE

INPUT
Nominal voltage (see series table)
Nominal frequency 50/60 Hz ±5Hz
Power factor > 0,98 – > 0,95 ( depends on model)
BYPASS
Voltage tolerance 180 – 264 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
Overload Times 125% for 4 seconds, 150% for 0,5 seconds
OUTPUT
Nominal voltage 220-230-240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50/60 Hz selectable
Static variation 1,5%
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor 3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 hours

Related Products