SR500L – SR750L – AC/DC Power Supplies – Battery Chargers 500W – 750W

The SRL models are designed for use as a precision AC to DC power supply, or a float charger for lead acid batteries. Note that for float charging the output voltage must be set to approximately 15% above the nominal battery voltage. The SRL series can have an optional ethernet, RS485 or RS232 communications port fitted.

 

SERIES TABLE

 Model Output (V) Output (A) Power (W)
SR500L12 13.8 36.2 (41.6 @ 12V) 500
SR500L24 24 20.8 500
SR500L30 30 16.6 500
SR500L36 36 13.8 500
SR500L48 48 10.4 500
SR500L60 60 8.3 500
SR500L91 96 5.2 500
SR500L92 108 4.6 500
SR500L93 120 4.1 500
SR750L12 13.8 36.2 (41.6 @ 12V) 750
SR750LA24 24 20.8 750
SR750L30 30 16.6 750
SR750L36 36 13.8 750
SR750L48 48 10.4 750
SR750L91 96 5.2 750
SR750L92 108 4.6 750
SR750L93 120 4.1 750

SPECIFICATIONS TABLE

ELECTRICAL
Input 180V – 264V ( 88V-132VAC option)
Frecuency 45-65Hz
Fusing Internal AC input fuse
Overcurrent protection Constant current limit under overload and short circuit conditions (except DC input versions which have primary current limit)
Isolation 1KV DC input – output / earth
Efficiency > 85%
Hold-up time 15 – 20 ms without batery
Alarms Mains fail (or PSU in standby mode)
DC low (Battery low or PSU low) – set at 92% of nominal voltage.
DC high
Alarm  relay contacts C – NO – NC changeover rated 1A /50V DC, 32VAC
MECHANICAL
AC Input Connector IEC320 inlet socket
Comms Choice of RS485 ,RS232, Ethernet
Protocols SNMP v1 or Modbus (external converter)
Dimensions 146.5 W x 62 H  x 177 D mm (SR100L) , 150W x 61H x 242D (SR250L)
Weight 0.94Kg (SR100L) , 1.7Kg(SR250L)
ENVIRONMENTAL
Operating temperature 0 – 50 °C ambient at full load De-rate linearly >50 °C to no load @ 70 °C
Storage temperature  -10 to 85 °C ambient
Humidity 0 – 95% relative humidity non-condensing
Cooling Fan cooled
STANDARDS 
Emi To CISPR 22 / EN55022 class A
Safety To IEC950 / EN60950 / AS/NZS3260